JP T2 4+0-350
|
|
SPD
according to EN 61643-11 / IEC 61643-11
|
Typ 2 / Class II
|
|
Nominal voltage UN
|
230 V
|
|
Maximum continuous operating
voltage UC
|
275 V / 385 V
|
|
Nominal
discharge current 8/20 μs In
|
20 kA
|
|
Maximum
discharge current 8/20 μs Imax
|
40 kA
|
|
Voltage
protection level UP
|
1.2 kV
|
|
Response time tA
|
25 ns
|
|
Maximum backup fuse
|
250 A
|
|
|
|
|
Dimensions W | H | D in mm
|
72 | 90 | 72
|
|
Horizontal pitch
|
4
|
|
Cross section solid
|
2,5 mm² – 50 mm²
|
|
Cross section flexible
|
2,5 mm² – 35 mm²
|
|
Temperature
|
-20 °C ... +80 °C
|
|
Degree of protection
|
IP 20
|