JP T1+T2 2+0-350
|
JP T1+T2 2+0-350 FM
|
SPD according to EN 61643-11 / IEC 61643-11
|
Typ 1 + Typ 2 / Class I + Class II
|
Typ 1 + Typ 2 / Class I + Class II
|
Nominal voltage UN
|
230 V
|
230 V
|
Maximum continuous operating voltage UC
|
260 V/ 385 V
|
260 V/ 385 V
|
Lightning impulse current 10/350 μs Iimp
|
35 kA
|
35 kA
|
Nominal discharge current 8/20 μs In
|
20 kA
|
20 kA
|
Voltage protection level UP
|
0.9 kV
|
0.9 kV
|
Short circuit withstand capability ISCCR
|
70 kA
|
70 kA
|
Response time tA
|
100 ns
|
100 ns
|
Maximum backup fuse - L
|
250 A
|
250 A
|
Maximum backup fuse - L-L‘
|
125 A
|
125 A
|
|
|
|
Dimensions W | H | D in mm
|
72 | 90 | 72
|
72 | 99 | 72
|
Horizontal pitch
|
4
|
4
|
Cross section solid
|
2.5 mm² – 50 mm²
|
2.5 mm² – 50 mm²
|
Cross section flexible
|
2.5 mm² – 35 mm²
|
2.5 mm² – 35 mm²
|
Temperature
|
-20 °C ... +80 °C
|
-20 °C ... +80 °C
|
Degree of protection
|
IP 20
|
IP 20
|
|
|
|
Remote signal contact
|
without
|
changer
|
Maximum voltage AC / DC
|
|
250 V / 250 V
|
Maximum current AC / DC
|
|
0.5 A / 0.1 A
|
Cross section
|
|
1.5 mm²
|
|
|