JP T1 + T2 4+0-350 |
JP T1 + T2 4+0-350 FM |
SPD according to EN 61643-11 / IEC 61643-11 |
Typ 1 + Typ 2 / Class I + Class II |
Typ 1 + Typ 2 / Class I + Class II |
Nominal voltage UN |
230 V |
230 V |
Maximum continuous operating voltage UC |
260 V/ 385 V |
260 V/ 385 V |
Lightning impulse current 10/350 μs Iimp |
35 kA |
35 kA |
Nominal discharge current 8/20 μs In |
20 kA |
3´20 kA |
Voltage protection level UP |
0.9 kV |
0.9 kV |
Short circuit withstand capability ISCCR |
140 kA |
140 kA |
Response time tA |
100 ns |
100 ns |
Maximum backup fuse - L |
250 A |
250 A |
Maximum backup fuse - L-L‘ |
125 A |
125 A |
|
|
|
Dimensions W | H | D in mm |
144 | 90 | 72 |
144 | 99 | 72 |
Horizontal pitch |
8 |
8 |
Cross section solid |
2.5 mm² – 50 mm² |
2.5 mm² – 50 mm² |
Cross section flexible |
2.5 mm² – 35 mm² |
2.5 mm² – 35 mm² |
Temperature |
-20 °C ... +80 °C |
-20 °C ... +80 °C |
Degree of protection |
IP 20 |
IP 20 |
|
|
|
Remote signal contact |
without |
changer |
Maximum voltage AC / DC |
|
250 V / 250 V |
Maximum current AC / DC |
|
0.5 A / 0.1 A |
Cross section |
|
1.5 mm² |
|
|
|