JMP T2 TNS 6B 40 385
|
JMP T2
TNS 6B 40 385 FM
|
SPD according to
|
EN 61643-11 /
IEC 61643-11
|
type 2 /
class II
|
type 2 / class II
|
Nominal voltage UN
|
230 V
|
230 V
|
Maximum continuous operating
voltage UC
|
385 V
|
385 V
|
Nominal discharge current 8/20 µs In
|
40 kA/MS/10P
|
40 kA/MS/10P
|
Maximum discharge current 8/20 µs Imax
|
60 kA
|
60 kA
|
Voltage protection level UP
|
1.5 kV
|
1.5 kV
|
Response
time tA
|
20 ns
|
20 ns
|
|
|
|
Dimensions B | H | T in mm
|
4 x 72 | 90 | 75
|
4 x 72 | 90 | 75
|
Horizontal pitch
|
16
|
16
|
Connection
data
|
solid
|
2.5 mm² – 35 mm²
|
2.5 mm² – 35 mm²
|
|
flexible
|
2.5 mm² – 25 mm²
|
2.5 mm² – 25 mm²
|
Operating temperature
|
-20 °C ... +80 °C
|
-20 °C ... +80 °C
|
Degree
of protection
|
IP 20
|
IP 20
|
|
|
|
Remote
signaling
|
without
|
changer
|
Maximum
voltage AC / DC
|
|
250 V / 30 V
|
Maximum
current AC / DC
|
|
1.5 A / 1.5 A
|
Connection
data
|
|
0.5 mm² – 1.5 mm²
|
-
Discharging up to 10 impulses
-
Voltage protection level under 1.5 kV
-
Usage for protection in TN-S systems
|
Product
|
Item number
|
without changer
|
JMP T2 TNS 6B 40 385
|
121011
|
with changer
|
JMP T2 TNS 6B 40 385 FM
|
121012
|